《Table 2 Voltage limit violations per case》

《Table 2 Voltage limit violations per case》   提示:宽带有限、当前游客访问压缩模式
本系列图表出处文件名:随高清版一同展现
《Identification of system vulnerabilities in the Ethiopian electric power system》


  1. 获取 高清版本忘记账户?点击这里登录
  1. 下载图表忘记账户?点击这里登录

Next,computer simulation is run for each line outage and,it is obtained that there are 28 severe line outages whose active power flow performance indices are greater than 1.0 pu and voltage level performance indices are greater than 0.02 pu.The ends of the transmission lines associated with the most severe line outages are labeled in Fig.3.It is evident that most of these line outages are predominantly along the highest voltage transmission lines(400 k V&230 k V)connecting the regional power systems of the country to the capital,Addis Ababa.Almost all of the line outages affect the high load centers,i.e.,Addis Ababa and central regions,as can be seen in Table 1 and Table2.This knowledge implies that as far as the transmission network is concerned,the main weaknesses of the EEP grid are on the lines feeding Addis Ababa and Central regions from the rest of the regional power systems.