《Table 1 Pre-synchronization switch closed condition》

《Table 1 Pre-synchronization switch closed condition》   提示:宽带有限、当前游客访问压缩模式
本系列图表出处文件名:随高清版一同展现
《Research on pre-synchronization control strategy of the micro-grid with multi-VSG》


  1. 获取 高清版本忘记账户?点击这里登录
  1. 下载图表忘记账户?点击这里登录

As Table.1 shows,the best closing time of presynchronization switch can be recognized by the sign of Uq,the angle frequency of micro-grid,and the angle phase|φ|.If these variables meet the conditions,pre-synchronization dynamic process will be Fig.4(c),so that the active power shock between multi-VSGs can be reduced.Because the range of?and?g changes periodically in[0,2π],it is difficult to determine if the phase difference in the control program is positive or negative.And Uq is the positive voltage synthesis vector in one and two quadrants,while it is negative in three and four quadrants.Therefore,using Uq and|φ|to control theφvalue before pre-synchronization within a certain range will effectively solve the problem of over-adjustment ofδvalue according to the relationship between the frequency value of micro-grid and power grid.The value of|φ|in this paper is shown in Table 1.