《Table 2 Mechanical results of composite insulators》
![《Table 2 Mechanical results of composite insulators》](http://bookimg.mtoou.info/tubiao/gif/GEIN201803011_10200.gif)
本系列图表出处文件名:随高清版一同展现
《Fiber Bragg grating monitors for thermal and stress of the composite insulators in transmission lines》
The results of the mechanical load tolerance are shown in Table 2 and Fig.2.The results show that the possibility of breakdown in the insulators increases with the running time,and the breakdown possibility is about 100%with the running time above 8 a,and the breakdown load is lower than 180 k N;the breakdown possibility of the socket is also higher than that of the ball;taking the insulator samples with the running time above 8 as an example,the breakdown possibility of the socket is 51.9%,and the possibility of the ball is 29.6%.
图表编号 | XD0020051500 严禁用于非法目的 |
---|---|
绘制时间 | 2018.08.01 |
作者 | Heming Deng、Wei Cai、You Song、Jinsong Liu、Christopher Redman、QiANDong Zhuang |
绘制单位 | NARI Group (State Grid Electric Power Research Institute) co.ltd、NARI Group (State Grid Electric Power Research Institute) co.ltd、NARI Group (State Grid Electric Power Research Institute) co.ltd、State Grid Xinjiang Electric Power Company、Physics departmen |